second version
This commit is contained in:
54
db/migration/V023__modbus_command_journal.sql
Normal file
54
db/migration/V023__modbus_command_journal.sql
Normal file
@@ -0,0 +1,54 @@
|
||||
-- Modbus command journal + cut-off switch audit (EMS)
|
||||
|
||||
CREATE TABLE ems.modbus_command (
|
||||
id SERIAL PRIMARY KEY,
|
||||
site_id INT NOT NULL REFERENCES ems.site(id),
|
||||
asset_type TEXT NOT NULL, -- 'inverter', 'ev_charger', 'heat_pump', 'cutoff'
|
||||
asset_id INT NOT NULL, -- ID v příslušné asset tabulce
|
||||
asset_code TEXT NOT NULL, -- např. 'deye-main' (denorm. pro čitelnost)
|
||||
device_host TEXT NOT NULL,
|
||||
device_port INT NOT NULL,
|
||||
device_unit_id INT NOT NULL,
|
||||
register INT NOT NULL, -- číslo registru (decimal)
|
||||
register_name TEXT, -- 'export_limit', 'charge_limit' (pro čitelnost)
|
||||
value_to_write INT NOT NULL,
|
||||
value_written INT, -- skutečně zapsaná hodnota (NULL = nezapsáno)
|
||||
value_verified INT, -- přečtená hodnota po verifikaci (NULL = neověřeno)
|
||||
status TEXT NOT NULL DEFAULT 'pending',
|
||||
-- 'pending', 'written', 'verified', 'failed', 'mismatch', 'retrying'
|
||||
planning_run_id INT REFERENCES ems.planning_run(id),
|
||||
attempt_count INT NOT NULL DEFAULT 0,
|
||||
created_at TIMESTAMPTZ NOT NULL DEFAULT now(),
|
||||
written_at TIMESTAMPTZ,
|
||||
verified_at TIMESTAMPTZ,
|
||||
error_msg TEXT
|
||||
);
|
||||
|
||||
COMMENT ON TABLE ems.modbus_command IS
|
||||
'Command journal pro Modbus zápisy do zařízení.
|
||||
Každý zápis = jeden řádek. Verifikační job ověří value_verified == value_to_write.
|
||||
Při mismatch: retry max 3× → přepnout na SELF_SUSTAIN + Discord alert.
|
||||
asset_type+asset_id odkazuje na příslušnou asset tabulku (inverter/ev_charger/...).';
|
||||
|
||||
CREATE INDEX idx_modbus_command_status
|
||||
ON ems.modbus_command (site_id, status, created_at DESC);
|
||||
|
||||
CREATE INDEX idx_modbus_command_pending
|
||||
ON ems.modbus_command (status, created_at)
|
||||
WHERE status IN ('pending', 'retrying');
|
||||
|
||||
CREATE TABLE ems.cutoff_switch_log (
|
||||
id SERIAL PRIMARY KEY,
|
||||
site_id INT NOT NULL REFERENCES ems.site(id),
|
||||
asset_code TEXT NOT NULL, -- 'cutoff-pv-b', 'cutoff-microinverter'
|
||||
switched_at TIMESTAMPTZ NOT NULL DEFAULT now(),
|
||||
new_state BOOLEAN NOT NULL, -- true=zapnuto/připojeno, false=odpojeno
|
||||
previous_state BOOLEAN,
|
||||
reason TEXT NOT NULL, -- 'negative_sell_price', 'manual', 'auto_restore'
|
||||
sell_price_czk NUMERIC(10,6), -- spotová cena v době přepnutí
|
||||
triggered_by TEXT -- 'control_exporter', 'user:jan', 'system'
|
||||
);
|
||||
|
||||
COMMENT ON TABLE ems.cutoff_switch_log IS
|
||||
'Log přepnutí cut-off přepínačů. Loguje se jen při změně stavu (edge trigger).
|
||||
Používá se pro mikroinvertory na GEN portu při záporných prodejních cenách.';
|
||||